Description
This Mitsubishi Heavy Industries SRK50ZS-S Air Conditioning System is Titanium and very stylish, the whole range is characterized by high flexibility, high energy efficiency and very low noise levels. The Mitsubishi air conditioning systems are available as standard and premium units. the Standard heat pump systems use inverter technologies whilst offering first-rate value for money, while premium models features the up-to-the-minute inverter technologies and high efficiency in heat pump technology, with a variation of added fun.
A range of compact and stylish indoor units are available in 6 different types, making air conditioning any indoor environment possible. Built in WiFi allows you to control your air conditioning from your smart device, anywhere.
Indoor / Outdoor Model No | SRK50ZS-WFT / SRC50ZS-W |
Nominal Cooling (Range) kW | 5.0 (1.7 – 5.5) |
UK Cooling (Total – Sensible) kW | 4.8 – 3.6 |
Nominal Heating (Range) kW | 5.8 (1.6 – 6.6) |
UK Heating kW | 4.2 |
SEER – SCOP (Cool – Heat) | 6.26 – 4.2 |
EER – COP (Cool – Heat) | 3.2 – 3.65 |
Energy Label (Cool – Heat) | A++ / A+ |
ECA | Yes |
Cooling °C | 46 to -15 |
Heating °C | 24 to -15 |
Indoor Unit Dimensions (H-W-D)mm | 290 – 870 – 230 |
Outdoor Unit Dimensions (H-W-D)mm | 595 – 780 (+62) – 290 |
Weight (Indoor – Outdoor) kg | 10 – 36.5 |
Indoor Unit Airflow Rate Cool (L-M-H) l/s | 7.4 – 9.9 – 12.1 |
Indoor Unit Airflow Rate Heat (L-M-H) l/s | 9.1 – 11.2 – 13.9 |
Static Pressure Pa | 0 |
Indoor Sound Pressure Cool (L-M-H) dB(A) | 28 – 36 – 45 |
Indoor Sound Pressure Heat (L-M-H) dB(A) | 31 – 37 – 45 |
Outdoor Sound Pressure (Cool – Heat) dB(A) | 51 – 53 |
Pipe Sizes (Gas – Liquid) in | 1/2″ & 1/4″ |
Pipe Limits (Max Run -Height Diff) m | 25 – 15 |
Pre Charged For (M) | 15 |
Charge R410a (Factory – Additional) | 1.25 – 20g/m |
Suitable for Replacement Tech | Yes |
Indoor Drain Connection (mm) | VP16 (14id 16 od) |
Power Supply (Outdoor) V – Ph – Hz | 230 – 1 – 50 |
Interconnecting Cable | 3 core + E |
Running Current (Cool – Heat) A | 6.9 – 7.3 |
Power Consumption (Cool – Heat) kW | 1.56 – 1.59 |
Start – Max Run Current (A) | 7.0 – 14.5 |
Suggested Fuse Size (A) | 20 |
<
Product reviews