Description
The Mitsubishi Electric PLA-ZM125EA Three Phase Power Inverter air conditioning heats cools and dehumidifies, The Dehumidification mode reduces uncomfortable humidity from the room without over cooling. The air conditioner will switch automatically from cooling to heating modes depending on the set temperature. The air vanes will be adjusted according to the mode of operation. In heating mode air will be distributed at a lower angle due to hot air rising. The indoor unit has a quiet operational noise of 27dB in quiet mode to offer you peace and quiet for the bedroom or office. In addition, the outdoor units have drastically reduced vibration and noise thanks to a super quiet fan and motor and an innovative anti noise mechanism.
Indoor Model No | PLA-ZM125EA |
Cooling Capacity (kW) | 12.5 (5.5 – 14.0) |
Heating Capacity (kW) | 14.0 (5.00 – 16.0) |
SHF (nominal) | 0.70 |
COP / EER (nominal) | 3.81 / 3.70 |
SCOP / SEER (BS EN14825) | 4.70 / 7.40 |
ERP Energy Efficiency Class Heating / Cooling | A++ / A++ |
Airflow (l/s) Lo – Mi – Mi2 – Hi | 350 – 400 – 433 – 483 |
Pipe Sizes MM (in) Gas / Liquid | 15.88 (5/8″) / 9.52 (3/8″) |
Sound Pressure Level (dBA) Lo – Mi – Mi2 – Hi | 33 – 36 – 39 – 41 |
Sound Power Level (dBA) | 62 |
Dimensions (mm) Width x Depth x Height (Grille) | 840 (950) x 840 (950) x 298 (40) |
Weight (kg) Unit / Grille) | 26 / 5 |
Electrical Supply | Fed by Outdoor Unit |
Fuse Rating (BS88) – HRC (A) | 6 |
Interconnecting Cables No. Cores | 4 |
Grille Reference | PLP-6EA |
Wired Remote Controller Reference | PAR-33MAA |
Outdoor Model No | PUZ-ZM125YKA |
Sound Pressure Level (dBA) Heating / Cooling | 52 / 50 |
Sound Power Level (dBA) Cooling | 70 |
Weight (kg) | 125 |
Dimensions (mm) Width x Depth x Height | 1050 x 330 + 40 x 1338 |
Electrical Supply | 380-415v, 50Hz |
Phase | Three |
System Power Input (kW) Heating / Cooling (nominal) | 3.674 / 3.378 |
System Power Input (kW) Heating / Cooling (UK) | 3.27 / 2.87 |
Starting Current (A) | 6.0 |
System Running Current (A) Heating / Cooling [Max] | 5.32 / 4.89 [10.0] |
Fuse Rating (BS88) – HRC (A) | 16 |
Mains Cable No. Cores | 5 |
Max Pipe Length (M) | 100 |
Max Height Difference (m) | 30 |
Charge Refrigerant (kg)/ R32 (GWP 675) – 30m
CO2 Equivalent (t) |
4.00 / 2.70 |
Max Additional Refrigerant kg) / R32 (GWP 675)
CO2 Equivalent (t) |
2.80 / 1.89 |
Product reviews