Description
Product Description
The Mitsubishi Electric MSZ-AP25VGK wall mounted air conditioning system is a wall mounted system that blends energy efficiency with a modern white design. The MSZ-AP25VGK has built in Wi-Fi allowing you to connect to the MELcloud app so you can control your air conditioning system from your mobile device. This unit also features a full weekly timer facility to give greater control of the system. This model also uses the latest R32 refrigerant to give high efficiency levels in both heating and cooling modes.
The MSZ–AY range is a wall-mounted system that combines energy efficiency with a sleek, modern white design. This mid-range unit offers exceptional benefits, including state-of-the-art Wi-Fi control as a standard feature and the use of low GWP R32 refrigerant.
Indoor Model No | MSZ-AY25VGK |
Heating (nominal) | 3.2 (1.0 – 4.1) |
Cooling (nominal) | 2.5 (0.9 – 3.4) |
Heating (UK) | 2.64 (0.8 – 3.4) |
Cooling (UK) | 2.48 (0.9 – 3.4) |
SHF (nominal) | 0.92 |
COP/EER (nominal) | 4.10 / 4.17 |
SCOP/SEER (BS 14825) | 4.80 / 8.60 |
Erp Energy Efficiency Class Heating/Cooling | A++ / A+++ |
Airflow (l/s) Heating (SLo-Lo-Mid-Hi-Shi) | 82-98-122-148-215 |
Airflow (l/s) Cooling (SLo-Lo-Mid-Hi-Shi) | 82-98-118-145-190 |
Pipe Sizes MM (in) | 9.52 (3/8″) / 6.35 (1/4″) |
Sound Pressure Level (dBA) – Heating (SLo-Lo-Mid-Hi-Shi) | 19-24-34-39-45 |
Sound Pressure Level (dBA) – Cooling (SLo-Lo-Mid-Hi-Shi) | 19-24-30-36-42 |
Sound Power Level (dBA) | 57 |
Dimensions (mm) WxDxH | 798 x 219 x 299 |
Weight (kg) | 10.5 |
Electrical Supply | Fed by Outdoor Unit |
Fuse Rating (BS88) – HRC (A) | 6 |
Interconnecting Cable No. Cores | 4 |
Outdoor Unit Model No | MUZ-AY25VG |
Sound Pressure Level (dBA) Heating / Cooling | 48 / 47 |
Sound Power Level (dBA) Cooling | 59 |
Weight (kg) | 31 |
Dimensions (mm) WxDxH | 800 x 285 x 550 |
Electrical Supply | 220-240v, 50Hz |
Phase | Single |
System Power Input (kW) Heating / Cooling -Nominal | 0.78 / 0.60 |
System Power Input (kW) Heating / Cooling -UK | 0.70 / 0.50 |
Starting Current (A) | 3.6 |
System Running Current (A) Heating / Cooling (Max) | 3.6 / 2.9 (7.06) |
Fuse Rating (BS88) – HRC (A) | 10 |
Mains Cable No. Cores | 3 |
Max Pipe Length (m) | 20 |
Max Height Difference (m) | 12 |
Charge Refrigerant (kg) / CO2 Equivalent (t) – R32 (GWP 675) – 7m | 0.55 / 0.37 |
Max Additional Refrigerant (kg) / CO2 Equivalent (t) – R32 (GWP 675) | 0.26 / 0.18 |